Fire and Smoke Dampers

Current Specification

All supply and return air ducts at AHU room crossings, fire wall crossings and at all floor crossings shall be provided with Fire damper (Manual / Motorized) of at least equal to the fire rating of the wall or floor on which it is installed as per UL555/UL555S 1995 tested by CBRI..

If motorized Fire Damper these shall be of multi-leaf type and provided with Spring Return electrical actuator having its own thermal trip for ambient air temperature outside the duct and air temperature inside the duct. Fire damper blades and outer frames shall be of 16G galvanized steel construction fitted with 16 Gauge extended sleeves on both sides.

Each fire/smoke damper shall be AMCA licensed and bear the AMCA seal for air Performance. Damper blades shall be airfoil shaped (equivalent to 2.3mm thickness strength) roll formed using 0.8mm thick single piece of galvanized sheet.

Pressure drop shall not exceed 7.5 Pa when tested at 300m/min face velocity on 600x600mm size damper. The electric actuator shall be energized either upon receiving a signal from smoke detector installed in AHU room supply air duct / return air duct or temperature sensor.

 

Recommended Change

All supply and return air ducts at AHU room crossings, fire wall crossings and at all floor crossings shall be provided with Motorized Fire & Smoke damper of at least equal to the fire rating of the wall or floor on which it is installed , Tested as per UL555 and leakage rating as per UL555S, tested & certified by UL.

Motorized Fire & Smoke Damper these shall be of multi-leaf type and provided with UL listed Spring Return electrical actuator. Each fire damper shall be provided with resettable thermal release which permits controlled closure of the damper at 74° C air temp inside the duct. Fire & Smoke damper blades and frames shall be of 16G, with minimum 180 GSM galvanized steel construction, fitted with 20Gauge extended sleeves on both sides.

The Damper Manufacturer must provide third party tested data for Air Performance. Damper blades shall be airfoil shaped (equivalent to 2.3mm thickness strength) roll formed using 0.8mm thick single piece of galvanized sheet or triple V type accurately formed using 16 Gauge Steel.

Pressure drop shall not exceed 20 Pa when tested at 300m/min face velocity on 600x600mm size damper. The electric actuator shall be De-energized either upon receiving a signal from smoke detector installed in AHU room supply air duct / return air duct or temperature sensor. The damper must be supplied in accordance with the maximum module & maximum assembly size mentioned in the UL certification of the manufacturer. The Actuator Sizing and Models must be in strict compliance with the manufacturer’s UL Damper Certification.

 

Reasoning

Fire & Smoke Dampers FSD cannot be Manually Operated, They need an Actuating Mechanism to Close/Open the Damper in event of Fire. The Fire Dampers Tested by CBRI are tested only for Limited tests as Per UL-555 only, such as Fire Endurance test & Hose Steam Hose test. The Fire Dampers tested by CBRI does not cover Smoke & leakage test, which are part of UL-555S. These are Life Safety product, so the Specs need to be stringent. There are many manufacturers in India offering UL certified FSD.

The Temperature Sensing device is not the part of the UL Listed Actuator. The UL listed Fire dampers should be constructed out of minimum 180 GSM Galvanized Steel Sheet (for corrosion resistance) and the Sleeve need not be 16Gauge. Even 20G gives enough stability.

These are Life Safety product, wherein UL Certification is most vital. AMCA testing is more related with Pressure drop data and limited to just 1-2 Manufacturers. Test Reports from other Third Party Inspection Agencies should also be accepted. UL Certified Dampers needn’t be Airfoil Blades. The Highest Class 1 leakage and the Fire Endurance test can be achieved with Triple V-type Blades, which are far more cost efficient.

Pressure Drop of Triple V type Blades are slightly Higher than the Airfoil Blades. Once again, these are Life Safety products used for emergency purpose, so more importance to be given to Fire & Smoke Leakage certification. In normal conditions, the Damper Actuator receives constant power, however in a Fire Condition, the  Actuator is De-energised so that the Damper Blades go into Fail-Safe Fire condition since the Actuators are Spring return type. The UL Certification of the Damper clearly mentions the minimum and the maximum sizes that can be supplied. It also prescribes the Actuator model to be used for various module sizes. The Life Safety Damper Supplies must be in accordance with these restrictions.

SHARE POST

WhatsApp
Email
Facebook
LinkedIn

Recent Posts

Disclaimer

All the information contained in this website  is provided for general information and reference purpose only. Caryaire Equipments India Private Limited does not represent or  warrant the information provided in this website is complete and accurate, nor that the information is up to date. The user must verify all the details and specifications, of the product from the Company prior to concluding any decision for buying any product. In no event shall the Company, their directors, employees and agents be liable to the user for any or all damages, losses and causes of action, errors, injury, whether direct, indirect, consequential or incidental, suffered or incurred by any person/s or due to any use and/or inability to use this website or information.